KIT Axpert VM III TWIN 6Kw 48V 6000-48 Solar Inverter Off Grid Island +

Voltronic Lio II-4810 Lifepo4 Battery Module 5.12Kw for inverter Voltronic, SP24, EASUN, ETC. Batteries with ground base and stackable up to 3 modules

Specifications Inverter • Current Power 6kw • TWIN: • Restorable battery power supply • Restorable battery power • Restorable battery power • Removable LCD control module with multiple communications • Built-in Wi-Fi for mobile monitoring (available Android/Iphone app) • Supports USB On-the-Go function • Reserved communication port for BMS (RS485) support x Pylontech US2000/3000, Yilink PV/100/150A

SPECIFICATIONS

Table 1 Specifications Line Mode

MODE INVERTER

   

4KW

   

6KW

   

Waveform input voltage

   

Sinusoidale (AC network or generator)

Rated input voltage

   

230Vac

Low Voltage Loss

   

170Vac±7V (UPS);

90Vac±7V (packing)

Fall Low Return Voltage

   

180Vac±7V (UPS);

100Vac±7V (Apparecchiature)

High Voltage Fall

   

280V

Fall Elevate Return Voltage

   

270Vac±7V

Tension Max. aC input

   

300Vac

Rated incoming

   

50Hz / 60Hz (Relevance)

Fall Low Frequency

   

40±1 Hz

Fall Low Return Voltage

   

42±1 Hz

Fall High Frequency

   

65±1 Hz

   

Fall Elevate Return Voltage

   

63±1 Hz

Protection against short circuit

   

Differential switch

Efficiency (Line Mode)

   

>95% (Nominal load R, fully charged battery)

Duration of transfer

   

10ms typical (UPS);

20ms typical (appearing);

Output power reduction

   

If the AC input voltage drops to 170 V, the output power will be reduced.

 

Table 2 Specifications Inverter Mode

   

MODE INVERTER

   

4KW

   

6KW

   

Nominal output power

   

4KVA/4KW

6KVA/6KW

Output voltage waveform

   

Pure sinusoidal wave

Output voltage adjustment

   

230Vac±10%

Output frequency

   

50 Hz

Peak efficiency

   

93%

Overload protection

   

5s@≥110% load; 10s@105%~110% load

Overload capacity

   

2* Rated power for 5 seconds

Max. Output AC current

30Amp

40Amp

Rated DC input voltage

   

24Vd

48Vdc

Cold Start Voltage

   

23.0Vdc

46.0Vdc

Low DC Alarm Voltage

   

23.0Vdc

22.0Vdc

 

46.0Vdc

44.0Vdc

@ load

@ load ≥ 50%

DC Low Alarm Back Voltage

   

23.5Vdc

23.0Vdc

47.0Vdc

46.0Vdc

@ load

@ load ≥ 50%

DC Low Cutoff Voltage

   

21.5Vdc

21.0Vdc

43.0Vdc

42.0Vdc

@ load

@ load ≥ 50%

DC High Recovery Voltage

   

32Vdc

62Vd

High DC cutoff voltage

   

33

63Vd

Consumption in load absence

   

 

Table 3 Charging Mode Specifications

   

AC Mains Charging Mode

   

MODE INVERTER

   

4KW

   

6KW

   

Charging algorithm

   

3-Step

   

AC charge current (max.)

   

100Amp

(TRANSLATED)I/P=230Vac)

Bulk charge voltage

   

Battery Lead-Acido

   

29.2Vdc

58,4

AGM/Gel battery

   

28.2Vdc

56,4

Float Voltage

   

27Vdc

54Vdc

Charging curve

   

Mode Charging Solar MPPT

MODE INVERTER

   

4KW

   

6KW

   

Max. Power array FV

   

5000W

6000W

Max. FV current

   

27A

Nominal PV voltage

   

320Vd

360Vdc

Start voltage

   

60Vdc +/- 10Vdc

Range voltage MPPT array FV

   

60Vdc~450Vdc

Max. Open circuit voltage FV array

   

500Vd

Maximum charge current

   

(More Solar Charger AC Charger)

   

120Amp

 

Table 4 General specifications

MODE INVERTER

   

4KW

   

6KW

   

Range operating temperature

   

- 10 °C + 50 °C

Storage temperature

   

-15°C~60°C

Relative humidity

   

5 - 95% relative humidity (without condensation)

Dimensions (P*L*H), mm

   

115 x 300 x 435

Net weight, kg

   

9

10

Specifications Battery

LIO II-4810 LIFEPO4 BATTERIA 5,12KW 48V

   

BATTERY MODULE

   

II-4810

   

CAPACITY

   

5120Wh

PARAMETER

   

Norminal Voltage

51.2VDC

Full Charge Voltage(FC)

56V

Full Discharge Voltage(FD)

42V

Typical Capacity

100 Ah

Max Continuous Discharging Current

150A

Max Discharging Current

192A at 1min

Protect

BMS, breaker

Charge Voltage

56V

Charge Current

20A (0.2C)

Maximum Charge current

50A (0.5C)

Standard Charge method

0.2C CC (Constant current) charge to FC, CV (Contstant voltage FC) charge till charge current decline to

Inner Resistance

≤20m ohm

PHYSICAL

   

Dimension, D X W X H (mm)

214 x 621 x 550

Net Weight (kgs)

55

*These figures may vary depending on different AC voltage and contry regulation.

Product specifications are subject to change without further notice

Please note the sale price of these products is with 10% VAT in case of purchase you will have to fill out a statement that the products will be used for a renewable energy plant The product is sold with reduced VAT to 10% exclusively to Italian residents with Italian shipping. In case of foreign customers please visit the section of the Inverter for EU countries website THE MODULE CAN BE FOUND HERE https://www.cercastock.it/repository/_barba_srl_dich_10.pdf THE PRODUCT WILL NOT BE DISPATCHED UNTIL YOU HAVE RECEIVED

Product Details
VOLTRONIC
KITVMIIITLIO
10 Items
Reviews

Write your review

Kit Voltronic Axpert VM III TWIN 6000watt 48V Off-Grid Inverter and Battery LIO-II 4810

Kit Voltronic Axpert VM III TWIN 6000watt 48V Off-Grid Inverter and Battery LIO-II 4810

Write your review
5 other products in the same category:

Follow us on Facebook